Smart trip logic for smart grids to block distance relay maloperation - Implementation and validation
Date Issued
01-12-2013
Author(s)
Abstract
Zone 1 reach setting of a distance relay depend upon many factors, such as, dc offset in current signals, loading effect, fault resistance in the presence of in-feed from remote end and also capacitive voltage transformer (CVT) transients. All these factors are taken care of except for CVT transients, which is dealt either by reducing zone 1 reach or by providing a fixed time delay in today's intelligent electronic devices (IED). This paper proposes a new and simple logic to prevent numerical distance relay mal-operation by zone 1 element due to CVT transients without sacrificing zone 1 reach. This is achieved by providing adaptive time delay by actually monitoring the CVT transients in time domain. The proposed logic is validated in real time by incorporating the proposed logic along with positive sequence polarized distance relay model in field programmable gate array (FPGA). © 2013 IEEE.