Abstract
This paper presents a high speed, computationally efficient scheme for protection of transmission lines. The relay logic consists of three parts: directional protection, fault classification and fault location. Wavelet transform is used for extracting information from the fault transients and only the first level high frequency details of the voltages and currents are used. Proposed protection logic compares the directional signals from both terminals to discriminate between faults inside and outside the zone of interest. Fault classification is achieved using local terminal current information. An estimate of the location of the faults is obtained utilizing single faulted phase current information from both terminals. The logic is deterministic and can work reliably in the presence of fault resistance, load variation and CT saturation. The validity of the proposed logic was exhaustively tested by simulating various types of faults on a four bus meshed system modeled in EMTP/ATP. © 2009 Elsevier Ltd. All rights reserved.
Volume
31