This paper reports the results of an experimental investigation of heat transfer from an internally finned thermosyphon charged with either water or acetone. Six constant area fins with a rectangular cross section are placed internally along the length at the condenser section. The ratio of initial liquid pool volume to the evaporator volume, known as the filling ratio in a thermosyphon system, has been varied in this study. Experiments are carried out for filling ratios of 20, 50, and 80% for two working fluids (i) water and (ii) acetone. Results show that a fill ratio of 50% gives better heat transfer performance. Providing internal fins at the condenser produces additional condensation which improves the thermal performance of the thermosyphon by 17% in terms of the temperature reduction at the source and sink and 35.48% in terms of reduction in thermal resistance at lower heat inputs. The thermosyphon is tested between power levels of 50 and 275 W.