Options
Performance analysis of a single stage four bed metal hydride cooling system, part B: Influence of heat recovery
Date Issued
01-01-2003
Author(s)
Abstract
Influence of heat recovery on the performance of a single stage multi-bed metal hydride cooling system is studied with Zr 0.9 Ti 0.1 CrFe and Zr 0.7 Ti 0.3 CrFe as high and low temperature alloys respectively. The heat recovery cycle effectively utilizes the sensible heat contained in the beds at the end of desorption and resorption processes thereby reducing the heat input and increasing the refrigerating effect. Compared to the basic cycle, the coefficient of performance of heat recovery cycle improves by about 15% to over 75% depending on the operating temperatures. © 2002 Éditions scientifiques et médicales Elsevier SAS. All rights reserved.
Volume
42