Options
Comparison of R22-absorbent pairs for absorption cooling based on P-T-X data
Date Issued
01-01-1993
Author(s)
Fatouh, M.
Srinivasa Murthy, S.
Abstract
P-T-X data for nine combinations of R22-absorbent solutions are presented as correlations. A comparative study of these working fluids in absorption refrigeration systems is made. Based on cut-off temperature and circulation ratio considerations DMEDEG, DMETEG, DMETrEG, DMF and DMA are preferable solvents for R22. Among these R22-DMF and R22-DMA stand out when the criterion of coefficient of performance is also included. The generator cut-off temperatures are correlated in terms of temperatures of absorber, condenser and evaporator. © 1993.
Volume
3